What size wire do I need for a 100 amp subpanel?
Table of Contents
What size wire do I need for a 100 amp subpanel?
#4
The cable must have a wire gauge sufficient to the amperage of the subpanel—a 100-amp subpanel requires #4 copper wires or, more commonly, #2 aluminum wires, for example. (Aluminum is often used for feeder cables because the cost is typically much lower than that of copper wires.)
Can you run a sub panel off a 100 amp panel?
First the panels you are looking at that are rated 100A simply means you can use them for any application up to 100A. You can for example add a 60A breaker to your existing panel and protect the new subpanel with a 100A rating.
Can an electrical sub panel feed another sub panel?
Yes, it’s redundant, but it’s still required. The wire feeding the new subpanel must be protected from overcurrent by an appropriately-sized breaker. It can be at either end – in the old subpanel or in the new subpanel – or at both ends.
How much can you run off a 100 amp panel?
Typical 100-amp panels have 20 circuits, meaning they can handle 20 full-sized breakers. 20/24 panels can hold 16 full-sized and 4 twin breakers (24 circuits in total). The number of breakers can max out to 30-42, too, depending on the design of your 100-amp pane.
Can I feed a 100 amp sub panel from a 200 amp service?
Yes that would work. Just make sure to keep your ground and neutral bars separated in the sub panel. Number 8 would be more than sufficient though as far as size goes. , Retired electrical engineer.
Can you have 2 subpanels?
You can add as many subpanels as you need providing the combined electrical demand is below 160 amps. If all the circuitry was operating at once, the electrical service could become overloaded. However, all combined circuitry would not likely be on at any given time.
Can I daisy chain subpanels?
You could daisy-chain a feeder from the main service panel (Panel A) to a subpanel (Panel B), and then run another feeder from Panel B to another subpanel (Panel C).
How many wires do I need to feed a subpanel?
A subpanel requires two hot wires connected to a 240-volt double-pole breaker in the main panel. It also needs a neutral wire and a ground wire. The cable used for this run is known as a “three-wire cable with ground.” The two hot wires, called feeder wires, will provide all of the power to the subpanel.